Table · NCC 2022 Volume One

Table D3D21a Wire barrier construction – minimum required tension (N) for stainless steel horizontal wires

Part D3 Construction of exits

Open Table D3D21a on NCC Online ↗
Wire dia. (mm)LayWire spacing (mm)Clear distance between posts (mm)
600800900100012001500180020002500
2.57x7605519026341547882310801139X
8038263073082410251288XXX
10086912181368XXXXXX
2.51x19603521831040258581011251325X
80420630735840105014001750XX
10011401565XXXXXXX
3.07x7601517827031450666096511681491
80250413500741818108313701565X
100865127813901639XXXXX
3.01x19602518326134052079010251180X
803255556707851015133017251980X
1001090150017051910XXXXX
4.07x760573971222354406648131178
801964224805247601100135815302130
1008351182136015281837238128113098X
4.01x1960551015201475938901280
80301923004155931105130314351844
10085313081487161020482608309434183849
4.07x1960155290358425599860108012851540
8039465478591511431485186021052615
100103814121598178521652735XXX

Table Notes

Lay = number of strands by the number of individual wires in each strand. For example a lay of 7x19 consists of 7 strands with 19 individual wires in each strand.

Where a change of direction is made in a run of wire, the tensioning device is to be placed at the end of the longest span.

If a 3.2 mm wire is used the tension figures for 3.0 mm wire are applied.

This table may also be used for a set of non-continuous (single) vertical wires forming a barrier using the appropriate clear distance between posts as the vertical clear distance between the rails.

X = Not allowed because the required tension would exceed the safe load of the wire.

Tension measured with a strain indicator.

Table for D3D21 Wire barriers

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table D3D21a.

Defined terms used