Table · NCC 2022 Volume One

Table D3D21b Continuous wire barrier construction – minimum required tension (N) for vertical or near-vertical stainless steel wires where the maximum clear spacing between the rails is 900mm

Part D3 Construction of exits

Open Table D3D21b on NCC Online ↗
Wire dia. (mm)LayWidest spacing between wires (mm)Required tension (N)
2.57x1980145
100310
110610
2.57x780130
100280
110500

Table Notes

Lay = number of strands by the number of individual wires in each strand. For example a lay of 7x19 consists of 7 strands with 19 individual wires in each strand.

Vertical wires require two pulley blocks to each 180° change of direction in the wire.

Near vertical wires may only require one pulley block for each change of direction.

Tension measured with a strain indicator.

The table only includes 7x7 and 7x19 wires due to other wires not having sufficient flexibility to make the necessary turns.

Table for D3D21 Wire barriers

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table D3D21b.