NCC 2022 Volume One
Part D3 Construction of exits
28 clauses · Open on NCC Online ↗
- D3D1 Deemed-to-Satisfy ProvisionsWhere a Deemed-to-Satisfy Solution is proposed, Performance Requirements D1P1 to D1P6, D1P8 and D1P9 are satisfied by complying with— D2D2 to D2D23,…
- D3D2 Application of Part NSWExcept for— D3D14, D3D15(a), D3D17, D3D18, D3D19, D3D20, D3D21, D3D22(5), D3D22(6), D3D26 and D3D29, the Deemed-to-Satisfy Provisions of this Part…
- D3D3 Fire-isolated stairways and rampsA stairway or ramp (including any landings) that is required to be within a fire-resisting shaft must be constructed— of non-combustible materials;…
- D3D4 Non-fire-isolated stairways and rampsIn a building having a rise in storeys of more than 2, required stairs and ramps (including landings and any supporting building elements) which are…
- D3D5 Separation of rising and descending stair flightsIf a stairway serving as an exit is required to be fire-isolated— there must be no direct connection between— a flight rising from a storey below…
- D3D8 Installations in exits and paths of travelAccess to service shafts and services other than to fire-fighting or detection equipment as permitted in the Deemed-to-Satisfy Provisions of Section…
- D3D9 Enclosure of space under stairs and rampsFire-isolated stairways and ramps — If the space below a required fire-isolated stairway or fire-isolated ramp is within the fire-isolated shaft, it…
- D3D11 Pedestrian rampsA fire-isolated ramp may be substituted for a fire-isolated stairway if the construction enclosing the ramp and the width and ceiling height comply…
- D3D12 Fire-isolated passagewaysThe enclosing construction of a fire-isolated passageway must have an FRL when tested for a fire outside the passageway in another part of the…
- Table D3D14 Riser and going dimensionsStairway location | Riser (R) | Going (G)Note 3 | Quantity (2R + G) Max | Min | Max | Min | Max | Min Public | 190 | 115 | 355 | 250 | 700 | 550…
- D3D14 Goings and risers NSWA stairway must have— not more than 18 and not less than 2 risers in each flight; and going (G), riser (R) and quantity (2R + G) in accordance with…
- Table D3D15 Slip-resistance classificationApplication | Dry surface conditions | Wet surface conditions Ramp steeper than 1:14 | P4 or R11 | P5 or R12 Ramp steeper than 1:20 but not steeper…
- D3D15 LandingsIn a stairway— landings having a maximum gradient of 1:50 may be used in any building to limit the number of risers in each flight and each landing…
- D3D17 Barriers to prevent fallsA continuous barrier must be provided along the side of— a roof to which general access is provided; and a stairway or ramp; and a floor, corridor,…
- D3D18 Height of barriers NSWThe height of a barrier required by D3D17 must be not less than the following: For stairways or ramps with a gradient of 1:20 or steeper — 865 mm.…
- D3D19 Openings in barriersExcept where allowed by (2), openings in a required barrier must not allow a 125 mm sphere to pass through. (2) In a fire-isolated stairway,…
- D3D20 Barrier climbabilityA barrier required by D3D17, located on a floor more than 4 m above the surface beneath, must not incorporate horizontal or near horizontal elements…
- Table D3D21a Wire barrier construction – minimum required tension (N) for stainless steel horizontal wiresWire dia. (mm) | Lay | Wire spacing (mm) | Clear distance between posts (mm) 600 | 800 | 900 | 1000 | 1200 | 1500 | 1800 | 2000 | 2500 2.5 | 7x7 |…
- Table D3D21b Continuous wire barrier construction – minimum required tension (N) for vertical or near-vertical stainless steel wires where the maximum clear spacing between the rails is 900mmWire dia. (mm) | Lay | Widest spacing between wires (mm) | Required tension (N) 2.5 | 7x19 | 80 | 145 100 | 310 110 | 610 2.5 | 7x7 | 80 | 130 100 |…
- Table D3D21c Wire barrier construction – maximum permissible deflection of each wire in mm when a 2 kg mass is suspended at mid-span for stainless steel wiresWire dia. (mm) | Wire spacing (mm) | Clear distance between posts (mm) 600 | 900 | 1200 | 1500 | 1800 | 2000 2.5 | 60 | 17 | 11 | 9 | 8 | 8 | 8 80 |…
- D3D21 Wire barriersWhere a required barrier is constructed of wire, it is deemed to meet the requirements of D3D19(1) if it is constructed in accordance with the…
- D3D22 HandrailsExcept for handrails referred to in D3D23, and subject to (2), handrails must— be located along at least one side of the ramp or flight; and be…
- D3D23 Fixed platforms, walkways, stairways and ladders SAA fixed platform, walkway, stairway, ladder and any going and riser, landing, handrail or barrier attached thereto may comply with AS 1657 in lieu…
- D3D24 Doorways and doors NSWA doorway in a resident use area of a Class 9c building must not be fitted with— a sliding fire door; or a sliding smoke door; or a revolving door;…
- D3D25 Swinging doors SAA swinging door in a required exit or forming part of a required exit— must not encroach— at any part of its swing by more than 500 mm on the…
- D3D27 Re-entry from fire-isolated exitsDoors of a fire-isolated exit must not be locked from the inside as follows: In a Class 9a health-care building. In a Class 9b early childhood…
- D3D29 Protection of openable windowsA window opening must be provided with protection, if the floor below the window is 2 m or more above the surface beneath in— a bedroom in a Class 2…
- D3D30 Timber stairways: ConcessionNotwithstanding D3D3(a), timber treads, risers, landings and associated supporting framework within a required fire-isolated stairway or…