Table · NCC 2022 Volume One
Table F1D8 Subfloor openings and ground clearance
Part F1 Surface water management, rising damp and external waterproofing
| Climatic zone (see Figure F1D8) | Minimum aggregate subfloor ventilation openings without a membrane (mm2/m of wall) | Minimum aggregate subfloor ventilation openings having the ground sealed with an impervious membrane (mm2/m of wall) | Minimum ground clearance height where termite inspection or management system is not required (mm) | Minimum ground clearance height where termite inspection is required (mm) Note 1 |
|---|---|---|---|---|
| A | 2000 | 1000 | 150 | 400 |
| B | 4000 | 2000 | 150 | 400 |
| C | 6000 | 3000 | 150 | 400 |
Table Notes
400 mm clearance required only where termite management systems are installed that need to be inspected (see B1D4).
On sloping sites, the 400 mm clearance required by (1) may be reduced to 150 mm within 2 m of external walls.
In situations where openings in external walls and internal subfloor walls are not able to be provided, additional measures must be provided to ensure that the overall level of ventilation of the subfloor space is maintained.
Additional measures referred to in (3) may include measures similar to those in F1D8(5), such as providing durability class timbers, or having the ground sealed in the subfloor space with an impervious membrane.
Not in NCC 2025. No Table F1D8 in NCC 2025 Volume One.