Table · NCC 2022 Volume One
Table F4D4c Sanitary facilities in Class 6 buildings – department stores, shopping centres
Part F4 Sanitary and other facilities
| User group | Facility type | Design occupancy | Number |
|---|---|---|---|
| Male patrons | Closet pans | 1 - 1200 | 1 |
| >1200 | Add 1 per 1200 | ||
| Urinals | 1 - 600 | 1 | |
| >600 | Add 1 per 1200 | ||
| Washbasins | 1 - 600 | 1 | |
| >600 | Add 1 per 1200 | ||
| Female patrons | Closet pans | 1 - 300 | 1 |
| 301 - 600 | 2 | ||
| >600 | Add 1 per 1200 | ||
| Washbasins | 1-600 | 1 | |
| 601 - 1200 | 2 | ||
| >1200 | Add 1 per 1200 |
Table Notes
Sanitary facilities need not be provided for patrons if the total number of persons accommodated in the building is not more than 600.
Table for F4D4 Facilities in Class 3 to 9 buildings
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table F4D4c.