Table · NCC 2025 Volume One

Table F4D4c Sanitary facilities in Class 6 buildings – department stores, shopping centres

Part F4 Sanitary and other facilities

Open Table F4D4c on NCC Online ↗
User groupFacility typeDesign occupancyNumber
Male patronsCloset pans1 - 12001
>1200Add 1 per 1200
Urinals1 - 6001
>600Add 1 per 1200
Washbasins1 - 6001
>600Add 1 per 1200
Female patronsCloset pans1 - 3001
301 - 6002
>600Add 1 per 1200
Washbasins1-6001
601 - 12002
>1200Add 1 per 1200

Table Notes

Sanitary facilities need not be provided for patrons if the total number of persons accommodated in the building is not more than 600.

Table for F4D4 Facilities in Class 3 to 9 buildings

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table F4D4c.