Table J3D12b Orientation sector summer exposure factor (Es) — climate zone 1

Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Open Table J3D12b on NCC Online ↗
P/HNorthNorth eastEastSouth eastSouthSouth westWestNorth west
0.000.620.760.790.750.520.891.060.85
0.050.520.670.730.680.450.820.980.75
0.100.490.610.680.650.410.760.920.69
0.200.440.530.620.570.330.660.800.60
0.400.360.410.480.420.250.530.660.47
0.600.300.330.400.360.200.420.530.38
0.800.260.280.320.280.180.360.460.32
1.000.230.230.270.250.150.300.380.28
1.200.210.210.230.200.130.270.340.26
1.400.200.190.200.180.130.220.300.22
1.600.180.160.170.160.110.200.270.21
1.800.150.160.160.130.100.200.240.18
2.000.140.150.140.130.100.170.220.17

Table for J3D12 External summer glazing of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D12b.