Table J3D12a Constant for Solar Heat Gain (CSHGC) — climate zones 1 to 7
| % Ventilation opening area per m2 | Climate zone 1 | Climate zone 2 | Climate zone 3 | Climate zone 4 | Climate zone 5 | Climate zone 6 | Climate zone 7 |
|---|---|---|---|---|---|---|---|
| 5% to <10% | 0.0191 | 0.0245 | 0.0547 | 0.0506 | 0.0674 | 0.1472 | 0.0930 |
| 10% to <15% | 0.0237 | 0.0532 | 0.0745 | 0.0946 | 0.1111 | 0.2969 | 0.2405 |
| 15% to <20% | 0.0294 | 0.0700 | 0.0861 | 0.1203 | 0.1367 | 0.3845 | 0.3267 |
| 20% to 90% | 0.0364 | 0.0819 | 0.0943 | 0.1385 | 0.1548 | 0.4466 | 0.3879 |
Table Notes
The ventilation opening area is the total area of each ventilation opening divided by the floor area of the storey, including any mezzanine.
No window can have a design ventilation opening greater than 90% because the window frame will always obstruct some area of the opening.
Interpolation is allowed for values between those shown.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D12a.