Table · NCC 2022 Volume One

Table J3D7b Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 1

Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Open Table J3D7b on NCC Online ↗
Roof ventilationReflective insulation under-roofUnder-roof insulation R-ValueSA ≤ 0.23SA > 0.23 to ≤ 0.32SA > 0.32 to ≤ 0.42SA > 0.42 to ≤ 0.53SA > 0.53 to ≤ 0.64
VentedYes< 1.01.51.51.51.52.0
≥ 1.0 to < 1.51.51.51.51.51.5
≥ 1.5 to < 2.01.51.51.51.51.5
≥ 2.01.51.51.52.02.0
No< 1.02.02.54.05.0X
≥ 1.0 to < 1.51.51.51.51.52.5
≥ 1.5 to < 2.01.51.51.52.02.0
≥ 2.01.51.51.51.51.5
StandardYes< 1.01.51.52.03.04.0
≥ 1.0 to < 1.51.51.51.51.52.5
≥ 1.5 to < 2.01.51.51.51.52.0
≥ 2.01.51.51.51.51.5
No< 1.02.54.06.0XX
≥ 1.0 to < 1.51.51.51.51.54.0
≥ 1.5 to < 2.01.51.52.02.02.5
≥ 2.01.51.51.52.02.5

Table Notes

SA = solar absorptance.

A roof space is to be considered ‘vented’ if it—

has one wind-driven roof ventilator per 50 m2 of ceiling area with gable, eave or ridge vents; or

has one powered roof ventilator per 200 m2 of ceiling area with gable, eave or ridge vents; or

is a tiled roof without sarking-type material at roof level.

If a roof is not ‘vented’, it is a ‘standard’ roof.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

X = not permitted.

Table for J3D7 Roofs and ceilings of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D7b.