Table · NCC 2022 Volume One

Table J3D7o Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 5

Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Open Table J3D7o on NCC Online ↗
Reflective insulation under- roofR-Value
Yes2.5
No3.0

Table Notes

The R-Value can be achieved by installing insulation under the roof or on top of the ceiling or a combination of both.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

Table for J3D7 Roofs and ceilings of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D7o.

Defined terms used