Table · NCC 2022 Volume One

Table J3D7w Adjusted minimum R-Value of ceiling insulation required to compensate for loss of ceiling insulation area

Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Open Table J3D7w on NCC Online ↗
Percentage of ceiling area uninsulatedMinimum R-Value of ceiling insulation required to satisfy J3D7(1) and J3D7(3)
1.01.52.02.53.03.54.04.55.05.5
0.5% to less than 1.0%1.01.62.22.83.44.04.75.46.26.9
1.0% to less than 1.5%1.11.72.32.93.64.45.26.17.0X
1.5% to less than 2.0%1.11.72.43.13.94.85.86.8XX
2.0% to less than 2.5%1.11.82.53.34.25.36.5XXX
2.5% to less than 3.0%1.21.92.63.64.65.9XXXX
3.0% to less than 4.0%1.22.03.04.25.7XXXXX
4.0% to less than 5.0%1.32.23.45.0XXXXXX

Table Notes

Interpolation is allowed for values between those shown.

X = not permitted.

Table for J3D7 Roofs and ceilings of a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D7w.