Table · NCC 2022 Volume One
Table J6D10 Maximum electric heating capacity
Part J6 Air-conditioning and ventilation
| Floor area of the conditioned space | W/m2 of floor area in climate zone 3 | W/m2 of floor area in climate zone 4 | W/m2 of floor area in climate zone 5 | W/m2 of floor area in climate zone 6 | W/m2 of floor area in climate zone 7 |
|---|---|---|---|---|---|
| ≤ 500 m2 | 50 | 60 | 55 | 65 | 70 |
| > 500 m2 | 40 | 50 | 45 | 55 | 60 |
Table for J6D10 Space heating
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J6D10.