Table · NCC 2022 Volume One

Table J6D10 Maximum electric heating capacity

Part J6 Air-conditioning and ventilation

Open Table J6D10 on NCC Online ↗
Floor area of the conditioned spaceW/m2 of floor area in climate zone 3W/m2 of floor area in climate zone 4W/m2 of floor area in climate zone 5W/m2 of floor area in climate zone 6W/m2 of floor area in climate zone 7
≤ 500 m25060556570
> 500 m24050455560

Table for J6D10 Space heating

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J6D10.