NCC 2022 Volume One
Part J6 Air-conditioning and ventilation
30 clauses · Open on NCC Online ↗
- J6D1 Deemed-to-Satisfy Provisions NSWWhere a Deemed-to-Satisfy Solution is proposed, Performance Requirements J1P1 to J1P4 are satisfied by complying with— J2D2; and J3D2 to J3D15; and…
- J6D2 Application of Part NSWThe Deemed-to-Satisfy Provisions of this Part do not apply to a Class 8 electricity network substation.
- Table J6D3 Requirement for an outdoor air economy cycleClimate zone | Total air flow rate requiring an economy cycle (L/s) 2 | 9000 3 | 7500 4 | 3500 5 | 3000 6 | 2000 7 | 2500 8 | 4000
- J6D3 Air-conditioning system controlAn air-conditioning system— must be capable of being deactivated when the building or part of a building served by that system is not occupied; and…
- Table J6D4 Required outdoor air treatmentClimate zone | Outdoor air flow (L/s) | Required measure 1 | >500 | Modulating control 2 | Not applicable | No required measure 3 | >1000 |…
- J6D4 Mechanical ventilation system controlGeneral — A mechanical ventilation system, including one that is part of an air-conditioning system, except where the mechanical system serves only…
- Table J6D5a Minimum fan performance gradeFan type | Installation type A or C | Installation type B or D Axial — as a component of an air handling unit or fan coil unit | 46.0 | 51.5 Axial —…
- Table J6D5b Fan regression coefficient aFan type | Fan motor input power < 10 kW | Fan motor input power ≥ 10 kW Axial | 2.74 | 0.78 Mixed flow | 4.56 | 1.1 Centrifugal forward-curved |…
- Table J6D5c Fan regression coefficient bFan type | Fan motor input power < 10 kW | Fan motor input power ≥ 10 kW Axial | 6.33 | 1.88 Mixed flow | 10.5 | 2.6 Centrifugal forward-curved |…
- Table J6D5d Maximum coil pressure dropNumber of rows | Maximum pressure drop (Pa) 1 | 30 2 | 50 4 | 90 6 | 130 8 | 175 10 | 220
- Table J6D5e Maximum clean filter pressure dropFilter minimum efficiency reporting value | Maximum pressure drop (Pa) 9 | 55 11 | 65 13 | 95 14 | 110
- J6D5 Fans and duct systemsFans, ductwork and duct components that form part of an air-conditioning system or mechanical ventilation system must— separately comply with (2),…
- Table J6D6 Ductwork and fittings – Minimum insulation R-ValueLocation of ductwork and fittings | Climate zone 1, 2, 3, 4, 5, 6 or 7 | Climate zone 8 Within a conditioned space | 1.2 | 2.0 Where exposed to…
- J6D6 Ductwork insulationDuctwork and fittings in an air-conditioning system must be provided with insulation— complying with AS/NZS 4859.1; and having an insulation R-Value…
- Table J6D8a Maximum pipework pressure drop – Non-distributive constant speed systemsNominal pipe diameter (mm) | Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m) | Maximum pressure drop in systems operating…
- Table J6D8b Maximum pipework pressure drop – Non-distributive variable speed systemsNominal pipe diameter (mm) | Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m) | Maximum pressure drop in systems operating…
- Table J6D8c Maximum pipework pressure drop – Distributive constant speed systemsNominal pipe diameter (mm) | Maximum pressure drop in systems operating 2000 hours/annum or less (Pa/m) | Maximum pressure drop in systems operating…
- Table J6D8d Maximum pipework pressure drop – Distributive variable speed systemsNominal pipe diameter (mm) | Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m) | Maximum pressure drop in systems operating…
- J6D8 Pump systemsGeneral — Pumps and pipework that form part of an air-conditioning system must either— separately comply with (2), (3) and (4); or achieve a pump…
- Table J6D9a Piping — Minimum insulation R-ValueFluid temperature | Minimum insulation R-Value nominal pipe diameter ≤ 40 mm | Minimum insulation R-Value — nominal pipe diameter > 40 mm and ≤ 80…
- Table J6D9b Vessels, heat exchangers and tanks — Minimum insulation R-ValueFluid temperature range | Minimum insulation R-Value Low temperature chilled — ≤ 2°C | 2.7 Chilled — > 2°C but ≤ 20°C | 1.8 Heated — > 30°C but ≤…
- J6D9 Pipework insulationPiping, vessels, heat exchangers and tanks containing heating or cooling fluid, where the fluid is held at a heated or cooled temperature, that are…
- Table J6D10 Maximum electric heating capacityFloor area of the conditioned space | W/m2 of floor area in climate zone 3 | W/m2 of floor area in climate zone 4 | W/m2 of floor area in climate…
- J6D10 Space heating NSWA heater used for air-conditioning or as part of an air-conditioning system must be— a solar heater; or a gas heater; or a heat pump heater; or a…
- Table J6D11a Minimum energy efficiency ratio for refrigerant chillers – Option 1Chiller type | Full load operation (Wr/Winput power) | Integrated part load (Wr/Winput power) Air-cooled chiller with a capacity ≤ 528 kWr | 2.985 |…
- Table J6D11b Minimum energy efficiency ratio for refrigerant chillers – Option 2Chiller type | Full load operation (Wr/Winput power) | Integrated part load (Wr/Winput power) Air-cooled chiller with a capacity ≤ 528 kWr | 2.866 |…
- J6D11 Refrigerant chillersAn air-conditioning system refrigerant chiller must comply with MEPS and the full load operation energy efficiency ratio and integrated part load…
- J6D12 Unitary air-conditioning equipmentUnitary air-conditioning equipment including packaged air-conditioners, split systems, and variable refrigerant flow systems must comply with MEPS…
- Table J6D13 Maximum fan motor power – Cooling towers, closed circuit coolers and evaporative condensersType | Cooling tower maximum fan motor input power (W/kWrej) | Closed circuit cooler maximum fan motor input power (W/kWrej) | Evaporative condenser…
- J6D13 Heat rejection equipmentThe motor rated power of a fan in a cooling tower, closed circuit cooler or evaporative condenser must not exceed the allowances in Table J6D13. (2)…