J6D10 Space heating
Part J6 Air-conditioning and ventilation · NCC 2019: J5.9
(1) A heater used for air-conditioning or as part of an air-conditioning system must be—
a solar heater; or
a gas heater; or
a heat pump heater; or
a heater using reclaimed heat from another process such as reject heat from a refrigeration plant; or
an electric heater if—
the heating capacity is not more than—
10 W/m2 of the floor area of the conditioned space in climate zone 1; or
40 W/m2 of the floor area of the conditioned space in climate zone 2; or
the value specified in Table J6D10 where reticulated gas is not available at the allotment boundary; or
the annual energy consumption for heating is not more than 15 kWh/m2 of the floor area of the conditioned space in climate zones 1, 2, 3, 4 and 5; or
the in-duct heater complies with J6D3(1)(b)(iii); or
any combination of (a) to (e).
(2) An electric heater may be used for heating a bathroom in a Class 2, 3, 9a or 9c building if the heating capacity is not more than 1.2 kW and the heater has a timer.
(3) A fixed heating or cooling appliance that moderates the temperature of an outdoor space must be configured to automatically shut down when—
there are no occupants in the space served; or
a period of one hour has elapsed since the last activation of the heater; or
the space served has reached the design temperature.
(4) A gas water heater, that is used as part of an air-conditioning system, must—
if rated to consume 500 MJ/hour of gas or less, achieve a minimum gross thermal efficiency of 86%; or
if rated to consume more than 500 MJ/hour of gas, achieve a minimum gross thermal efficiency of 90%.
Table J6D10 Maximum electric heating capacity
Floor area of the conditioned space
W/m2 of floor area in climate zone 3
W/m2 of floor area in climate zone 4
W/m2 of floor area in climate zone 5
W/m2 of floor area in climate zone 6
W/m2 of floor area in climate zone 7
≤ 500 m2
50
60
55
65
70
> 500 m2
40
50
45
55
60
Tables
Changed in NCC 2025. See NCC 2025 Volume One J6D10, or show what changed.
(1) A heater used for air-conditioning or as part of … solar heater; or a gas heater; or a heat pump heater; heater or 4-pipe chiller; or a heater using reclaimed heat from another process such as reject heat from a refrigeration plant; or an electric resistance heater if — the heating capacity is not more than — 10 W/m2 of the floor area of the conditioned space in climate zone 1; or 40 W/m2 of the floor area of the conditioned space in climate zone zones 1 or 2; or the value specified in Table J6D10 where reticulated gas is not available at the allotment boundary; in climate zones 3 to 8; or the annual energy consumption for heating is not more … 3, 4 and 5; or the in-duct heater complies with J6D3(1)(b)(iii); or J6D3(1)(c)(iv);or any combination of (a) to (e). (2) An electric resistance heater may be used for heating a bathroom in a Class 2, 3, 9a or 9c building if — the heating capacity is not more than 1.2 kW kW; and the heater has a timer. time switch configured to deactivate the heater after a run-on period not more than 15 minutes from when there are no occupants in the space served. (3) A fixed heating or cooling appliance that moderates the temperature of an outdoor space must — be a radiant heater or evaporative cooler; and be configured to automatically shut down when — there are … a period of one hour has elapsed since the last activation of the heater; activation; or the space served has reached the design temperature. temperature for heating; or the space served has reached the design temperature for 30 minutes for cooling. (4) A gas water heater, that is used as part of an air-conditioning system, must — if rated to consume 500 MJ/hour of gas or less, achieve a minimum gross thermal efficiency of 86%; or if rated to consume more than 500 MJ/hour of gas, achieve a minimum gross thermal efficiency of 90%. (5) A building with gas space heating must be provided with — reserved electrical capacity sufficient to support future installation of — an electric resistance space heating system with a heating capacity of not more than the value specified in J6D10(1)(e)(i) or (ii); or air-source heat pump water heating equipment assuming a nominal coefficient of performance of 3.25; or a combination of (i) and (ii); and reserved space within the main electrical distribution board, labelled accordingly, sized to facilitate future installation of switchgear and electrical supply for electric space heating equipment sized in accordance with (a); and reserved space in the electrical riser or supply pathway for future electric space heating equipment sized in accordance with (a). (6) Where reserved capacity for air-source heat pump water heating equipment is required by (5), the building must be provided with — reserved space for an open-roofed plant room or rooftop plant area with — an area of at least 36 m² plus 0.04 m²/kW of heating capacity to facilitate future installation of air-source heat pump water heating equipment; and sufficient ventilation openings to achieve airflow of at least 100 L/s per kW of heating capacity to facilitate future air-source heat pump equipment, with no recirculation of air; and connection to the space heating hot water system; and a hot water circulation system that can deliver the design heating load at a peak temperature of less than 50°C. (7) Capacity and space required by (5) and (6) must be sufficient to serve all of the conditioned space with the same design load used to specify the gas space heater equipment. (8) A connected group of one or more air-source heat pump water heaters, including 4-pipe chillers used as part of an air-conditioning system, must — when operating in heating mode have a capacity-weighted average coefficient of performance of not less than 3.14 at intermediate temperature and standard rating conditions as specified in Table 13 of EN 14511-2; and when operating in cooling mode — have a capacity-weighted average energy efficiency ratio at full load of not less than — 2.9 when determined in accordance with AHRI 551/591; or 2.9 when determined at the standard rating conditions specified in Table 16 of EN 14511-2; and have a capacity-weighted average part load performance assessed based on — integrated part load value of not less than 4.69 when determined in accordance with AHRI 551/591; or Seasonal Energy Efficiency Ratio of 3.91 when determined in accordance with methods of Part 5 of EN 14825, at the standard part load conditions defined in Part 4 of EN 14825. (9) The capacity-weighted average of each efficiency metric in (8) must be calculated in accordance with the following formula: [formula] where — [formula] = the number of heat pump water heaters in the group; and [formula] = the capacity of each heater, [formula] , in either heating or cooling mode as applicable; and [formula] = the rated coefficient of performance, energy efficiency ratio, or integrated part load value of each heater, [formula] as applicable. Table J6D10 Maximum electric resistance heating capacity Floor area of the conditioned space W/m2 of … 65 70 > 500 m2 40 50 45 55 60