Table · NCC 2022 Volume One
Table J6D13 Maximum fan motor power – Cooling towers, closed circuit coolers and evaporative condensers
Part J6 Air-conditioning and ventilation
| Type | Cooling tower maximum fan motor input power (W/kWrej) | Closed circuit cooler maximum fan motor input power (W/kWrej) | Evaporative condenser maximum fan motor input power (W/kWrej) |
|---|---|---|---|
| Induced draft | 10.4 | 16.9 | 11.0 |
| Forced draft | 19.5 | Note | 11.0 |
Table Notes
A closed circuit, forced draft cooling tower must not be used.
Table for J6D13 Heat rejection equipment
Changed in NCC 2025 (minor wording). See NCC 2025 Volume One Table J6D13, or show what changed.
Type | Cooling tower maximum fan motor input power (W/kWrej) (W/kW) | Closed circuit cooler maximum fan motor input power (W/kWrej) (W/kW) | Evaporative condenser maximum fan motor input power (W/kWrej) (W/kW) Induced draft | 10.4 | 16.9 | 11.0 Forced draft … closed circuit, forced draft cooling tower must not be used.
Removed words are struck through; added words are highlighted. Comparison of the text only.