Deemed-to-Satisfy Provision · NCC 2022 Volume One

J6D12 Unitary air-conditioning equipment

Part J6 Air-conditioning and ventilation · NCC 2019: J5.11

Open J6D12 on NCC Online ↗

Unitary air-conditioning equipment including packaged air-conditioners, split systems, and variable refrigerant flow systems must comply with MEPS and for a capacity greater than or equal to 65 kWr—

where water cooled, have a minimum energy efficiency ratio of 4.0 Wr/Winputpower for cooling when tested in accordance with AS/NZS 3823.1.2 at test condition T1, where input power includes both compressor and fan input power; or

where air cooled, have a minimum energy efficiency ratio of 2.9 Wr/Winput power for cooling when tested in accordance with AS/NZS 3823.1.2 at test condition T1, where input power includes both compressor and fan input power.

Changed in NCC 2025. See NCC 2025 Volume One J6D12, or show what changed.

Unitary air-conditioning equipment (1) Water-to-air unitary air-conditioners with a rated capacity greater than or equal to 65 kW, including packaged air-conditioners, split systems, and variable refrigerant flow systems units, must comply with MEPS and for a capacity greater than or equal to 65 kWr — where water cooled, have a minimum energy efficiency ratio of 4.0 Wr/Winputpower for cooling when tested in accordance with AS/NZS 3823.1.2 at test condition T1, where input power includes both compressor and fan input power; or where air cooled, have a minimum energy efficiency ratio of 2.9 Wr/Winput power for cooling when tested in accordance with AS/NZS 3823.1.2 ISO 13256.1 at test condition T1, C3, where input power includes both compressor and fan input power. (2) Assessed individually or collectively, a building’s air-cooled unitary air-conditioning equipment, including packaged air-conditioners, split systems, and variable refrigerant flow units, must have a weighted efficiency index greater than 1 — calculated using the following formula, based on the energy efficiency ratio, [formula] , where — [formula] = the weighted efficiency index of the unitary air-conditioners serving a building, assessed based on their rated Energy Efficiency Ratios; and for each air-conditioner, [formula] — [formula] = the tested energy efficiency ratio, determined in accordance with MEPS; and [formula] = the rated cooling capacity determined in accordance with MEPS; and [formula] = the applicable nominal minimum energy efficiency ratio in Table J6D12a; or calculated using the following formula, based on the Total Cooling Seasonal Performance Factor, [formula] , where — [formula] = the weighted efficiency index of the unitary air-conditioners serving a building, assessed based on their rated Total Cooling Seasonal Performance Factors; and for each air-conditioner, [formula] — [formula] = the mixed zone Total Cooling Seasonal Performance Factor, determined in accordance with MEPS for the commercial based use of the product; and [formula] = the rated cooling capacity determined in accordance with MEPS; and [formula] = the applicable nominal minimum energy efficiency ratio in Table J6D12b. (3) Where the weighted efficiency index contribution of an air-conditioner is assessed using the formula at (2)(a), air-cooled unitary air-conditioners, including packaged air-conditioners, split systems and variable refrigerant flow units, must have — variable speed outdoor fans; and at least one — digital scroll compressor; or inverter driven compressor. (4) The compressor required by 3(b) must be sized sufficiently to allow the unit to modulate across 50% to 100% of its rated cooling capacity. (5) The requirements of (2) to (4) do not apply to — unitary air-conditioners with a rated cooling capacity of less than 10 kW; or unitary air-conditioners that serve only a Class 4 part of a building. Table J6D12a Nominal minimum energy efficiency ratio figures for air-cooled unitary air-conditioning systems Rated cooling capacity Unitary systems other than variable refrigerant flow units Variable refrigerant flow units ≤ 39 kW 3.3 3.8 > 39 kW 3.1 3.4 Table J6D12b Nominal minimum TCSPF figures for air-cooled unitary air-conditioning systems Rated cooling capacity Unitary systems other than variable refrigerant flow units ≤ 30 kW 3.6 > 30 kW 3.5

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J6D12? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →