Table · NCC 2022 Volume One
Table J6D3 Requirement for an outdoor air economy cycle
Part J6 Air-conditioning and ventilation
| Climate zone | Total air flow rate requiring an economy cycle (L/s) |
|---|---|
| 2 | 9000 |
| 3 | 7500 |
| 4 | 3500 |
| 5 | 3000 |
| 6 | 2000 |
| 7 | 2500 |
| 8 | 4000 |
Table for J6D3 Air-conditioning system control
Changed in NCC 2025 (minor wording). See NCC 2025 Volume One Table J6D3, or show what changed.
Climate zone | Total air flow rate requiring an economy … | 7500 4 | 3500 5 | 3000 6 | 2000 1200 7 | 2500 8 | 4000 2000
Removed words are struck through; added words are highlighted. Comparison of the text only.