Table · NCC 2022 Volume One
Table J6D9b Vessels, heat exchangers and tanks — Minimum insulation R-Value
Part J6 Air-conditioning and ventilation
| Fluid temperature range | Minimum insulation R-Value |
|---|---|
| Low temperature chilled — ≤ 2°C | 2.7 |
| Chilled — > 2°C but ≤ 20°C | 1.8 |
| Heated — > 30°C but ≤ 85°C | 3.0 |
| High temperature heated — > 85°C | 3.0 |
Table for J6D9 Pipework insulation