Table · NCC 2022 Volume One

Table J6D9b Vessels, heat exchangers and tanks — Minimum insulation R-Value

Part J6 Air-conditioning and ventilation

Open Table J6D9b on NCC Online ↗
Fluid temperature rangeMinimum insulation R-Value
Low temperature chilled — ≤ 2°C2.7
Chilled — > 2°C but ≤ 20°C1.8
Heated — > 30°C but ≤ 85°C3.0
High temperature heated — > 85°C3.0

Table for J6D9 Pipework insulation

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J6D9b.