Table S35C2k Occupancy and operation profiles of a Class 9c aged care facility
Specification 35 Modelling profiles for J1V3
| Time period (local standard time) | Occupancy (Monday to Friday) | Occupancy (Saturday, Sunday and holidays) | Artificial lighting (Daily) | Air-conditioning (Monday to Friday) | Air-conditioning (Saturday, Sunday and holidays) |
|---|---|---|---|---|---|
| 12:00am to 1:00am | 85% | 85% | 5% | On | On |
| 1:00am to 2:00am | 85% | 85% | 5% | On | On |
| 2:00am to 3:00am | 85% | 85% | 5% | On | On |
| 3:00am to 4:00am | 85% | 85% | 5% | On | On |
| 4:00am to 5:00am | 85% | 85% | 5% | On | On |
| 5:00am to 6:00am | 85% | 85% | 25% | On | On |
| 6:00am to 7:00am | 85% | 85% | 80% | On | On |
| 7:00am to 8:00am | 80% | 85% | 80% | On | On |
| 8:00am to 9:00am | 50% | 50% | 50% | On | On |
| 9:00am to 10:00am | 10% | 50% | 20% | Off | On |
| 10:00am to 11:00am | 10% | 20% | 20% | Off | Off |
| 11:00am to 12:00pm | 10% | 20% | 20% | Off | Off |
| 12:00pm to 1:00pm | 10% | 20% | 20% | Off | Off |
| 1:00pm to 2:00pm | 10% | 20% | 20% | Off | Off |
| 2:00pm to 3:00pm | 10% | 20% | 20% | Off | Off |
| 3:00pm to 4:00pm | 10% | 30% | 20% | Off | Off |
| 4:00pm to 5:00pm | 50% | 50% | 20% | On | On |
| 5:00pm to 6:00pm | 50% | 50% | 50% | On | On |
| 6:00pm to 7:00pm | 70% | 50% | 50% | On | On |
| 7:00pm to 8:00pm | 70% | 70% | 50% | On | On |
| 8:00pm to 9:00pm | 80% | 80% | 50% | On | On |
| 9:00pm to 10:00pm | 85% | 80% | 50% | On | On |
| 10:00pm to 11:00pm | 85% | 85% | 50% | On | On |
| 11:00pm to 12:00am | 85% | 85% | 5% | On | On |
Table Notes
The occupancy profile is expressed as a percentage of the maximum number of people that can be accommodated in the Class 9c building.
The artificial lighting profile is expressed as a percentage of the maximum illumination power density permitted under Part J7.
The air-conditioning profile is expressed as the plant status.
Table for S35C2 Modelling profiles
Changed in NCC 2025. See NCC 2025 Volume One Table S35C2k, or show what changed.
Time period (local standard time) | Occupancy (Monday to Friday) … | 50% | On | On 9:00am to 10:00am | 10% 50% | 50% | 20% | Off | On 10:00am to 11:00am | 10% 50% | 20% 50% | 20% | Off | Off On 11:00am to 12:00pm | 10% 50% | 20% 50% | 20% | Off | Off On 12:00pm to 1:00pm | 10% 50%5 | 20% 50% | 20% | Off | Off On 1:00pm to 2:00pm | 10% 50% | 20% 50% | 20% | Off | Off On 2:00pm to 3:00pm | 10% 50% | 20% 50% | 20% | Off | Off On 3:00pm to 4:00pm | 10% 50% | 30% 50% | 20% | Off | Off On 4:00pm to 5:00pm | 50% | 50% | 20% | … J7. The air-conditioning profile is expressed as the plant status.
Removed words are struck through; added words are highlighted. Comparison of the text only.