Table S35C2l Internal heat gains for appliances and equipment

Specification 35 Modelling profiles for J1V3

Open Table S35C2l on NCC Online ↗
ApplicationInternal sensible heat gain rate
Class 9a building ward area5 W/m2 averaged for 24 hours per day, 7 days per week, continuous operation
Class 8 laboratory and a Class 9a clinic, day surgery and a procedure unit15 W/m2
Class 6 shop and shopping centre, Class 6 cafe and restaurant and Class 9b school5 W/m2
Other applicationsNo load
Class 3 (sole-occupancy unit)160 W per room
Class 3 dormitoriesNo load
Class 5 building11 W/m2
Class 9c building160 W per room
Class 9b (conference facilities only)150 W per room plus 10 W per person

Table for S35C2 Modelling profiles

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S35C2l.