Table · NCC 2022 Volume One
Table S35C2l Internal heat gains for appliances and equipment
Specification 35 Modelling profiles for J1V3
| Application | Internal sensible heat gain rate |
|---|---|
| Class 9a building ward area | 5 W/m2 averaged for 24 hours per day, 7 days per week, continuous operation |
| Class 8 laboratory and a Class 9a clinic, day surgery and a procedure unit | 15 W/m2 |
| Class 6 shop and shopping centre, Class 6 cafe and restaurant and Class 9b school | 5 W/m2 |
| Other applications | No load |
| Class 3 (sole-occupancy unit) | 160 W per room |
| Class 3 dormitories | No load |
| Class 5 building | 11 W/m2 |
| Class 9c building | 160 W per room |
| Class 9b (conference facilities only) | 150 W per room plus 10 W per person |
Table for S35C2 Modelling profiles
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S35C2l.