Table · NCC 2022 Volume One

Table S45C3n Wind pressure coefficients for natural ventilation of low-rise buildings (total height less than 12 m)

Specification 45 Modelling profiles for J1V5

Open Table S45C3n on NCC Online ↗
Exposure typeFaçade componentWind direction (0° perpendicular to face)
04590135180
ExposedWall0.70035-0.50-0.40-0.20
Roof pitch < 10 degrees-0.80-0.70-0.60-0.50-0.40
Roof pitch 10 to 30 degrees-0.40-0.50-0.60-0.50-0.40
Roof pitch > 30 degrees0.30-0.40-0.60-0.40-0.50
Semi-exposedWall0.400.10-0.30-0.35-0.20
Roof pitch < 10 degrees-0.60-0.50-0.40-0.50-0.60
Roof pitch 10 to 30 degrees-0.35-0.45-0.55-0.45-0.35
Roof pitch > 30 degrees0.30-0.50-0.60-0.50-0.50
ShelteredWall0.200.05-0.25-0.30-0.25
Roof pitch < 10 degrees-0.50-0.50-0.40-0.50-0.50
Roof pitch 10 to 30 degrees-0.30-0.40-0.50-0.40-0.30
Roof pitch > 30 degrees0.25-0.30-0.50-0.30-0.40

Table Notes

Pressure coefficient exposure categories are defined as follows:

Exposed – no obstructions surrounding the building (e.g. open fields or bodies of water).

Semi-exposed – some obstructions comparable to the height of the building on some but not all sides.

Sheltered – obstructions comparable to the height of the building on all sides.

Table for S45C3 Proposed building and reference building

Not in NCC 2025. No Table S45C3n in NCC 2025 Volume One.