Table · NCC 2022 Volume One
Table S45C3o Wind pressure coefficients for natural ventilation of high-rise building (total height more than 12 m)
Specification 45 Modelling profiles for J1V5
| Exposure type | Façade component | Wind direction (0° perpendicular to face) | ||||
|---|---|---|---|---|---|---|
| 0 | 45 | 90 | 135 | 180 | ||
| Exposed | Wall h/H = 0.0 | 0.30 | 0.22 | -0.23 | -0.43 | -0.24 |
| Wall h/H = 0.2 | 0.32 | 0.22 | -0.43 | -0.44 | -0.25 | |
| Wall h/H = 0.4 | 0.39 | 0.16 | -0.56 | -0.43 | -0.27 | |
| Wall h/H = 0.6 | 0.55 | 0.24 | -0.62 | -0.41 | -0.29 | |
| Wall h/H = 0.8 | 0.65 | 0.32 | -0.65 | -0.39 | -0.28 | |
| Wall h/H = 1.0 | 0.40 | 0.15 | -0.65 | -0.38 | -0.26 | |
| Flat roof h/H = 0.0 | -0.23 | -0.23 | -0.23 | -0.23 | -0.23 | |
| Flat roof h/H = 0.2 | -0.43 | -0.43 | -0.43 | -0.43 | -0.43 | |
| Flat roof h/H = 0.4 | -0.56 | -0.56 | -0.56 | -0.56 | -0.56 | |
| Flat roof h/H = 0.6 | -0.62 | -0.62 | -0.62 | -0.62 | -0.62 | |
| Flat roof h/H = 0.8 | -0.65 | -0.65 | -0.65 | -0.65 | -0.65 | |
| Flat roof h/H = 1.0 | -0.65 | -0.65 | -0.65 | -0.65 | -0.65 | |
| Semi-exposed | Wall h/H = 0.0 | 0.19 | 0.08 | -0.15 | -0.28 | -0.15 |
| Wall h/H = 0.2 | 0.20 | 0.08 | -0.28 | -0.29 | -0.16 | |
| Wall h/H = 0.4 | 0.25 | 0.10 | -0.36 | -0.28 | -0.18 | |
| Wall h/H = 0.6 | 0.36 | 0.16 | -0.40 | -0.27 | -0.19 | |
| Wall h/H = 0.8 | 0.42 | 0.20 | -0.42 | -0.25 | -0.18 | |
| Wall h/H = 1.0 | 0.26 | 0.10 | -0.42 | -0.25 | -0.17 | |
| Flat roof h/H = 0.0 | -0.15 | -0.15 | -0.15 | -0.15 | -0.15 | |
| Flat roof h/H = 0.2 | -0.28 | -0.28 | -0.28 | -0.28 | -0.28 | |
| Flat roof h/H = 0.4 | -0.36 | -0.36 | -0.36 | -0.36 | -0.36 | |
| Flat roof h/H = 0.6 | -0.40 | -0.40 | -0.40 | -0.40 | -0.40 | |
| Flat roof h/H = 0.8 | -0.42 | -0.42 | -0.42 | -0.42 | -0.42 | |
| Flat roof h/H = 1.0 | -0.42 | -0.42 | -0.42 | -0.42 | -0.42 | |
| Sheltered | Wall h/H = 0.0 | 0.10 | 0.04 | -0.08 | -0.15 | -0.08 |
| Wall h/H = 0.2 | 0.11 | 0.04 | -0.15 | -0.15 | -0.08 | |
| Wall h/H = 0.4 | 0.13 | 0.05 | -0.19 | -0.15 | -0.09 | |
| Wall h/H = 0.6 | 0.19 | 0.08 | -0.21 | -0.14 | -0.10 | |
| Wall h/H = 0.8 | 0.22 | 0.11 | -0.22 | -0.13 | -0.09 | |
| Wall h/H = 1.0 | 0.32 | 0.05 | -0.22 | -0.13 | -0.09 | |
| Flat roof h/H = 0.0 | -0.08 | -0.08 | -0.08 | -0.08 | -0.08 | |
| Flat roof h/H = 0.2 | -0.15 | -0.15 | -0.15 | -0.15 | -0.15 | |
| Flat roof h/H = 0.4 | -0.19 | -0.19 | -0.19 | -0.19 | -0.19 | |
| Flat roof h/H = 0.6 | -0.21 | -0.21 | -0.21 | -0.21 | -0.21 | |
| Flat roof h/H = 0.8 | -0.22 | -0.22 | -0.22 | -0.22 | -0.22 | |
| Flat roof h/H = 1.0 | -0.22 | -0.22 | -0.22 | -0.22 | -0.22 |
Table Notes
Pressure coefficient exposure categories are defined as follows:
Exposed – no obstructions surrounding the building (e.g. open fields or bodies of water).
Semi-exposed – some obstructions comparable to the height of the building on some but not all sides.
Sheltered – obstructions comparable to the building height on all sides.
h = height of natural ventilation opening above ground.
H = height of roof of building above ground.
Table for S45C3 Proposed building and reference building
Not in NCC 2025. No Table S45C3o in NCC 2025 Volume One.