Table · NCC 2022 Volume One

Table S45C3o Wind pressure coefficients for natural ventilation of high-rise building (total height more than 12 m)

Specification 45 Modelling profiles for J1V5

Open Table S45C3o on NCC Online ↗
Exposure typeFaçade componentWind direction (0° perpendicular to face)
04590135180
ExposedWall h/H = 0.00.300.22-0.23-0.43-0.24
Wall h/H = 0.20.320.22-0.43-0.44-0.25
Wall h/H = 0.40.390.16-0.56-0.43-0.27
Wall h/H = 0.60.550.24-0.62-0.41-0.29
Wall h/H = 0.80.650.32-0.65-0.39-0.28
Wall h/H = 1.00.400.15-0.65-0.38-0.26
Flat roof h/H = 0.0-0.23-0.23-0.23-0.23-0.23
Flat roof h/H = 0.2-0.43-0.43-0.43-0.43-0.43
Flat roof h/H = 0.4-0.56-0.56-0.56-0.56-0.56
Flat roof h/H = 0.6-0.62-0.62-0.62-0.62-0.62
Flat roof h/H = 0.8-0.65-0.65-0.65-0.65-0.65
Flat roof h/H = 1.0-0.65-0.65-0.65-0.65-0.65
Semi-exposedWall h/H = 0.00.190.08-0.15-0.28-0.15
Wall h/H = 0.20.200.08-0.28-0.29-0.16
Wall h/H = 0.40.250.10-0.36-0.28-0.18
Wall h/H = 0.60.360.16-0.40-0.27-0.19
Wall h/H = 0.80.420.20-0.42-0.25-0.18
Wall h/H = 1.00.260.10-0.42-0.25-0.17
Flat roof h/H = 0.0-0.15-0.15-0.15-0.15-0.15
Flat roof h/H = 0.2-0.28-0.28-0.28-0.28-0.28
Flat roof h/H = 0.4-0.36-0.36-0.36-0.36-0.36
Flat roof h/H = 0.6-0.40-0.40-0.40-0.40-0.40
Flat roof h/H = 0.8-0.42-0.42-0.42-0.42-0.42
Flat roof h/H = 1.0-0.42-0.42-0.42-0.42-0.42
ShelteredWall h/H = 0.00.100.04-0.08-0.15-0.08
Wall h/H = 0.20.110.04-0.15-0.15-0.08
Wall h/H = 0.40.130.05-0.19-0.15-0.09
Wall h/H = 0.60.190.08-0.21-0.14-0.10
Wall h/H = 0.80.220.11-0.22-0.13-0.09
Wall h/H = 1.00.320.05-0.22-0.13-0.09
Flat roof h/H = 0.0-0.08-0.08-0.08-0.08-0.08
Flat roof h/H = 0.2-0.15-0.15-0.15-0.15-0.15
Flat roof h/H = 0.4-0.19-0.19-0.19-0.19-0.19
Flat roof h/H = 0.6-0.21-0.21-0.21-0.21-0.21
Flat roof h/H = 0.8-0.22-0.22-0.22-0.22-0.22
Flat roof h/H = 1.0-0.22-0.22-0.22-0.22-0.22

Table Notes

Pressure coefficient exposure categories are defined as follows:

Exposed – no obstructions surrounding the building (e.g. open fields or bodies of water).

Semi-exposed – some obstructions comparable to the height of the building on some but not all sides.

Sheltered – obstructions comparable to the building height on all sides.

h = height of natural ventilation opening above ground.

H = height of roof of building above ground.

Table for S45C3 Proposed building and reference building

Not in NCC 2025. No Table S45C3o in NCC 2025 Volume One.