Table S5C11g Type A construction: FRL of other building elements not covered by Tables S5C11a to S5C11f
Specification 5 Fire-resisting construction
| Building element | FRL (in minutes): Structural adequacy / Integrity / Insulation | |||
|---|---|---|---|---|
| Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 | |
| Other loadbearing internal walls, internal beams, trusses and columns | 90/–/– | 120/–/– | 180/–/– | 240/–/– |
| Floors | 90/90/90 | 120/120/120 | 180/180/180 | 240/240/240 |
| Roofs | 90/60/30 | 120/60/30 | 180/60/30 | 240/90/60 |
Table for S5C11 Type A fire-resisting construction — fire-resistance of building elements