Table · NCC 2022 Volume One

Table S5C11g Type A construction: FRL of other building elements not covered by Tables S5C11a to S5C11f

Specification 5 Fire-resisting construction

Open Table S5C11g on NCC Online ↗
Building elementFRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 partClass 5, 7a or 9Class 6Class 7b or 8
Other loadbearing internal walls, internal beams, trusses and columns90/–/–120/–/–180/–/–240/–/–
Floors90/90/90120/120/120180/180/180240/240/240
Roofs90/60/30120/60/30180/60/30240/90/60

Table for S5C11 Type A fire-resisting construction — fire-resistance of building elements

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S5C11g.

Defined terms used