S5C11 Type A fire-resisting construction — fire-resistance of building elements
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 3.1 and Table 3
(1) In a building required to be of Type A construction—
each building element listed in Tables S5C11a, S5C11b, S5C11c, S5C11d, S5C11e, S5C11f and S5C11g, and any beam or column incorporated in it, must have an FRL not less than that listed in those Tables for the particular class of building concerned; and
any internal wall required to have an FRL with respect to integrity and insulation must extend to—
the underside of the floor next above; or
the underside of a roof complying with Table S5C11g; or
if under S5C15 the roof is not required to comply with Table S5C11g, the underside of the non-combustible roof covering and, except for roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not be crossed by timber or other combustible building elements; or
a ceiling that is immediately below the roof and has a resistance to the incipient spread of fire to the roof space between the ceiling and the roof of not less than 60 minutes; and
a loadbearing internal wall and a loadbearing fire wall (including those that are part of a loadbearing shaft) must be constructed from—
concrete; or
masonry; or
subject to (2), fire-protected timber; or
any combination of (i) to (iii); and
the FRLs specified in Table S5C11c for an external column apply also to those parts of an internal column that face and are within 1.5 m of a window and are exposed through that window to a fire-source feature.
(2) For the purposes of (1)(c)(iii), fire-protected timber may be used, provided that—
the building is—
a separate building; or
a part of a building—
which only occupies part of a storey, and is separated from the remaining part by a fire wall; or
which is located above or below a part not containing fire-protected timber and the floor between the adjoining parts is provided with an FRL not less than that prescribed for a fire wall for the lower storey; and
the building has an effective height of not more than 25 m; and
the building has a sprinkler system (other than a FPAA101D or FPAA101H system) throughout complying with Specification 17; and
any insulation installed in the cavity of the timber building element required to have an FRL is non-combustible; and
cavity barriers are provided in accordance with Specification 9.
(3) For the purposes of Table S5C11a and Table S5C11b, external wall includes any column and other building element incorporated within it or other external building element.
Table S5C11a Type A construction: FRL of loadbearing parts of external walls
Distance from a fire-source feature
FRL (in minutes): Structural adequacy/ Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Less than 1.5 m
90/90/90
120/120/120
180/180/180
240/240/240
1.5 to less than 3 m
90/60/60
120/90/90
180/180/120
240/240/180
3 m or more
90/60/30
120/60/30
180/120/90
240/180/90
Table S5C11b Type A construction: FRL of non-loadbearing parts of external walls
Distance from a fire-source feature
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Less than 1.5 m
–/90/90
–/120/120
–/180/180
–/240/240
1.5 to less than 3 m
–/60/60
–/90/90
–/180/120
–/240/180
3 m or more
–/–/–
–/–/–
–/–/–
–/–/–
Table S5C11c Type A construction: FRL of external columns not incorporated in an external wall
Column type
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Loadbearing
90/–/–
120/–/–
180/–/–
240/–/–
Non-loadbearing
–/–/–
–/–/–
–/–/–
–/–/–
Table S5C11d Type A construction: FRL of common walls and fire walls
Wall type
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Loadbearing or non-loadbearing
90/90/90
120/120/120
180/180/180
240/240/240
Table S5C11e Type A construction: FRL of loadbearing internal walls
Location
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Fire-resisting lift and stair shafts
90/90/90
120/120/120
180/120/120
240/120/120
Bounding public corridors, public lobbies and the like
90/90/90
120/–/–
180/–/–
240/–/–
Between or bounding sole-occupancy units
90/90/90
120/–/–
180/–/–
240/–/–
Ventilating, pipe, garbage, and like shafts not used for the discharge of hot products of combustion
90/90/90
120/90/90
180/120/120
240/120/120
Table S5C11f Type A construction: FRL of non-loadbearing internal walls
Location
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Fire-resisting lift and stair shafts
–/90/90
–/120/120
–120/120
–/120/120
Bounding public corridors, public lobbies and the like
–/60/60
–/–/–
–/–/–
–/–/–
Between or bounding sole-occupancy units
–/60/60
–/–/–
–/–/–
–/–/–
Ventilating, pipe, garbage, and like shafts not used for the discharge of hot products of combustion
–/90/90
–/90/90
–/120/120
–/120/120
Table S5C11g Type A construction: FRL of other building elements not covered by Tables S5C11a to S5C11f
Building element
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Other loadbearing internal walls, internal beams, trusses and columns
90/–/–
120/–/–
180/–/–
240/–/–
Floors
90/90/90
120/120/120
180/180/180
240/240/240
Roofs
90/60/30
120/60/30
180/60/30
240/90/60
Tables
- Table S5C11a Type A construction: FRL of loadbearing parts of external walls
- Table S5C11b Type A construction: FRL of non-loadbearing parts of external walls
- Table S5C11c Type A construction: FRL of external columns not incorporated in an external wall
- Table S5C11d Type A construction: FRL of common walls and fire walls
- Table S5C11e Type A construction: FRL of loadbearing internal walls
- Table S5C11f Type A construction: FRL of non-loadbearing internal walls
- Table S5C11g Type A construction: FRL of other building elements not covered by Tables S5C11a to S5C11f
Changed in NCC 2025. See NCC 2025 Volume One S5C11, or show what changed.
(1) In a building required to be of Type A … the roof of not less than 60 minutes; and a loadbearing load bearing internal wall and a loadbearing load bearing fire wall (including those that are part of a loadbearing load bearing shaft) must be constructed from — concrete; or masonry; or subject to (2), fire-protected timber; or subject to (3), fire-protected steel; or any combination of (i) to (iii); (iv); and the FRLs specified in Table S5C11c for an external … in accordance with Specification 9. (3) For the purposes of (1)(c)(iv), fire-protected steel may be used in a Class 2 or 3 building or the uppermost storey of any other building classification, provided that — the building is — a separate building; or a part of a building — which only occupies part of a storey, and is separate from the remaining part by a fire wall; or which is located above a part not containing fire-protected steel and the floor between adjoining parts is provided with an FRL, not less than that prescribed for a fire wall for the lower storey; and the building has an effective height of not more than 25 m; and the building has a sprinkler system (other than a FPAA101D or FPAA101H system) throughout complying with Specification 17; and any insulation installed in the cavity of walls required to have an FRL is non-combustible; and at each floor level, any cavity within a wall required to have an FRL that provides a vertically continuous gap to the level above is interrupted by a cavity barrier in the form of a steel member, steel sheet of 0.5 mm base metal thickness or greater, a 16 mm thick or greater fire-protective grade plasterboard or a 45 mm thick or greater mineral wool barrier. (4) For the purposes of Table S5C11a and Table S5C11b, external wall includes any column … walls Distance from a fire-source feature FRL (in minutes): Structural adequacy/ adequacy / Integrity / Insulation Class 2, 3 or 4 part Class … 5, 7a or 9 Class 6 Class 7b or 8 Loadbearing Load bearing 90/–/– 120/–/– 180/–/– 240/–/– Non-loadbearing Non-load bearing –/–/– –/–/– –/–/– –/–/– Table S5C11d Type A construction: FRL … 5, 7a or 9 Class 6 Class 7b or 8 Loadbearing Load bearing or non-loadbearing non-load bearing 90/90/90 120/120/120 180/180/180 240/240/240 Table S5C11e Type A construction: FRL … 7a or 9 Class 6 Class 7b or 8 Other loadbearing load bearing internal walls, internal beams, trusses and columns 90/–/– 120/–/– 180/–/– 240/–/– Floors 90/90/90 120/120/120 180/180/180 240/240/240 Roofs 90/60/30 120/60/30 180/60/30 240/90/60
Removed words are struck through; added words are highlighted. Comparison of the text only.