Table · NCC 2022 Volume One
Table S5C11f Type A construction: FRL of non-loadbearing internal walls
Specification 5 Fire-resisting construction
| Location | FRL (in minutes): Structural adequacy / Integrity / Insulation | |||
|---|---|---|---|---|
| Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 | |
| Fire-resisting lift and stair shafts | –/90/90 | –/120/120 | –120/120 | –/120/120 |
| Bounding public corridors, public lobbies and the like | –/60/60 | –/–/– | –/–/– | –/–/– |
| Between or bounding sole-occupancy units | –/60/60 | –/–/– | –/–/– | –/–/– |
| Ventilating, pipe, garbage, and like shafts not used for the discharge of hot products of combustion | –/90/90 | –/90/90 | –/120/120 | –/120/120 |
Table for S5C11 Type A fire-resisting construction — fire-resistance of building elements
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S5C11f.