Table · NCC 2025 Volume One
Table S5C21f Type B construction: FRL of non-loadbearing internal walls
Specification 5 Fire-resisting construction
| Location | FRL (in minutes): Structural adequacy / Integrity / Insulation | |||
|---|---|---|---|---|
| Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 | |
| Fire-resisting stair shafts | –/90/90 | –/120/120 | –/120/120 | –/120/120 |
| Bounding public corridor, public lobbies and the like | –/60/60 | –/–/– | –/–/– | –/–/– |
| Between or bounding sole-occupancy units | –/60/60 | –/–/– | –/–/– | –/–/– |
Table for S5C21 Type B fire-resisting construction — fire-resistance of building elements
Changed since NCC 2022 (minor wording). See NCC 2022 Volume One Table S5C21f, or show what changed.
Location | FRL (in minutes): Structural adequacy / Integrity / … 9 | Class 6 | Class 7b or 8 Fire-resisting lift and stair shafts | –/90/90 | –/120/120 | –/120/120 | –/120/120 … sole-occupancy units | –/60/60 | –/–/– | –/–/– | –/–/–