Table · NCC 2022 Volume One
Table S5C24c Type C construction: FRL of common walls and fire walls
Specification 5 Fire-resisting construction
| Wall type | FRL (in minutes): Structural adequacy / Integrity / Insulation | |||
|---|---|---|---|---|
| Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 | |
| Loadbearing or non-loadbearing | 90/90/90 | 90/90/90 | 90/90/90 | 90/90/90 |
Table for S5C24 Type C fire-resisting construction — fire-resistance of building elements
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S5C24c.