S5C24 Type C fire-resisting construction — fire-resistance of building elements
Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 5.1 and Table 5
(1) In a building required to be of Type C construction—
a building element listed in Tables S5C24a, S5C24b, S5C24c, S5C24d and S5C24e and any beam or column incorporated in it, must have an FRL not less than that listed in those Tables for the particular Class of building concerned; and
an external wall that is required by Table S5C24a to have an FRL need only be tested from the outside to satisfy the requirement; and
a fire wall or an internal wall bounding a sole-occupancy unit or separating adjoining units must comply with Specification 6 if it is of lightweight construction and is required to have an FRL; and
in a Class 2 or 3 building, an internal wall which is required by Table 5C24c or S5C24d to have an FRL must extend—
to the underside of the floor next above if that floor has an FRL of at least 30/30/30 or a fire-protective covering on the underside of the floor; or
to the underside of a ceiling having a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
to the underside of the roof covering if it is non-combustible, and except for roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not be crossed by timber or other combustible building elements; or
450 mm above the roof covering if it is combustible; and
in a Class 2 or 3 building, except where within the one sole-occupancy unit, or a Class 9a health-care building, or a Class 9b building, a floor separating storeys, or above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, and any column supporting the floor, must—
have an FRL of at least 30/30/30; or
have a fire-protective covering on the underside of the floor including beams incorporated in it and around the column, if the floor or column is combustible or of metal; and
in a Class 9c building a floor above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, and any column supporting the floor, must—
have an FRL of at least 30/30/30; or
have a fire-protective covering on the underside of the floor including beams incorporated in it and around the column, if the floor or column is combustible or of metal.
(2) For the purposes of Table S5C24a and Table S5C24b, external wall includes any column and other building element incorporated within it or other external building element.
Table S5C24a Type C construction: FRL of parts of external walls
Distance from a fire-source feature
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Less than 1.5 m
90/90/90
90/90/90
90/90/90
90/90/90
1.5 to less than 3 m
–/–/–
60/60/60
60/60/60
60/60/60
3 m or more
–/–/–
–/–/–
–/–/–
–/–/–
Table S5C24b Type C construction: FRL of external columns not incorporated into an external wall
Distance from a fire-source feature
FRL (in minutes): structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Less than 1.5 m
90/–/–
90/–/–
90/–/–
90/–/–
1.5 to less than 3 m
–/–/–
60/–/–
60/–/–
60/–/–
3 m or more
–/–/–
–/–/–
–/–/–
–/–/–
Table S5C24c Type C construction: FRL of common walls and fire walls
Wall type
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Loadbearing or non-loadbearing
90/90/90
90/90/90
90/90/90
90/90/90
Table S5C24d Type C construction: FRL of internal walls
Location
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Bounding public corridors, public lobbies and the like
60/60/60
–/–/–
–/–/–
–/–/–
Between or bounding sole-occupancy units
60/60/60
–/–/–
–/–/–
–/–/–
Bounding a stair if required to be rated
60/60/60
60/60/60
60/60/60
60/60/60
Table S5C24e Type C construction: FRL of roof
Location
FRL (in minutes): Structural adequacy / Integrity / Insulation
Class 2, 3 or 4 part
Class 5, 7a or 9
Class 6
Class 7b or 8
Roofs
–/–/–
–/–/–
–/–/–
–/–/–
Tables
- Table S5C24a Type C construction: FRL of parts of external walls
- Table S5C24b Type C construction: FRL of external columns not incorporated into an external wall
- Table S5C24c Type C construction: FRL of common walls and fire walls
- Table S5C24d Type C construction: FRL of internal walls
- Table S5C24e Type C construction: FRL of roof
Changed in NCC 2025. See NCC 2025 Volume One S5C24, or show what changed.
(1) In a building required to be of Type C … or 3 building, an internal wall which is required by Table 5C24c S5C24c or S5C24d to have an FRL must extend — to … 5, 7a or 9 Class 6 Class 7b or 8 Loadbearing Load bearing or non-loadbearing non-load bearing 90/90/90 90/90/90 90/90/90 90/90/90 Table S5C24d Type C construction: FRL … 6 Class 7b or 8 Roofs –/–/– –/–/– –/–/– –/–/–