Table · NCC 2022 Volume One
Table S5C24b Type C construction: FRL of external columns not incorporated into an external wall
Specification 5 Fire-resisting construction
| Distance from a fire-source feature | FRL (in minutes): structural adequacy / Integrity / Insulation | |||
|---|---|---|---|---|
| Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 | |
| Less than 1.5 m | 90/–/– | 90/–/– | 90/–/– | 90/–/– |
| 1.5 to less than 3 m | –/–/– | 60/–/– | 60/–/– | 60/–/– |
| 3 m or more | –/–/– | –/–/– | –/–/– | –/–/– |
Table for S5C24 Type C fire-resisting construction — fire-resistance of building elements
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S5C24b.