Table · NCC 2022 Volume One
Table S5C7 Increased FRLs — Construction surrounding mezzanines
Specification 5 Fire-resisting construction
| Level otherwise required for any FRL criterion (mins) | Increase in level to not less than (mins) |
|---|---|
| 30 | 60 |
| 60 | 90 |
| 90 | 120 |
| 120 | 180 |
| 180 | 240 |
Table Notes
The increase in level applies to each FRL criterion (structural adequacy, integrity or insulation) relevant to the building element concerned.
Table for S5C7 Mezzanine floors: Concession
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table S5C7.