Table S5C7 Increased FRLs — Construction surrounding mezzanines

Specification 5 Fire-resisting construction

Open Table S5C7 on NCC Online ↗
Level otherwise required  for any FRL criterion (mins)Increase in level to not less than (mins)
3060
6090
90120
120180
180240

Table Notes

The increase in level applies to each FRL criterion (structural adequacy, integrity or insulation) relevant to the building element concerned.

Table for S5C7 Mezzanine floors: Concession

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S5C7.