Table S7C3 Critical radiant flux (CHF in kW/m2) of floor linings and floor coverings

Specification 7 Fire hazard properties

Open Table S7C3 on NCC Online ↗
Class of buildingBuilding not fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17Building fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17Fire-isolated exits and fire control rooms
Class 2, 3, 5, 6, 7, 8 or 9b, excluding Class 3 accommodation for the aged and Class 9b as specified below2.2 kW/m21.2 kW/m22.2 kW/m2
Class 3 accommodation for the aged4.5 kW/m22.2 kW/m24.5 kW/m2
Class 9a patient care areas4.5 kW/m22.2 kW/m24.5 kW/m2
Class 9a areas other than patient care areas2.2 kW/m21.2 kW/m24.5 kW/m2
Class 9b auditorium or audience seating area used mainly for indoor swimming or ice skating1.2 kW/m21.2 kW/m22.2 kW/m2
Class 9b auditorium or audience seating area used mainly for other sports or multi-purpose functions2.2 kW/m21.2 kW/m22.2 kW/m2
Class 9c resident use areaN/A2.2 kW/m24.5 kW/m2
Class 9c areas other than resident use areasN/A1.2 kW/m24.5 kW/m2

Table for S7C3 Floor linings and floor coverings