Table · NCC 2025 Volume One
Table S7C3 Critical radiant flux (CHF in kW/m2) of floor linings and floor coverings
Specification 7 Fire hazard properties
| Class of building | Building not fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 | Building fitted with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 | Fire-isolated exits and fire control rooms |
|---|---|---|---|
| Class 2, 3, 5, 6, 7, 8 or 9b, excluding Class 3 accommodation for the aged and Class 9b as specified below | 2.2 kW/m2 | 1.2 kW/m2 | 2.2 kW/m2 |
| Class 3 accommodation for the aged | 4.5 kW/m2 | 2.2 kW/m2 | 4.5 kW/m2 |
| Class 9a patient care areas | 4.5 kW/m2 | 2.2 kW/m2 | 4.5 kW/m2 |
| Class 9a areas other than patient care areas | 2.2 kW/m2 | 1.2 kW/m2 | 4.5 kW/m2 |
| Class 9b auditorium or audience seating area used mainly for indoor swimming or ice skating | 1.2 kW/m2 | 1.2 kW/m2 | 2.2 kW/m2 |
| Class 9b auditorium or audience seating area used mainly for other sports or multi-purpose functions | 2.2 kW/m2 | 1.2 kW/m2 | 2.2 kW/m2 |
| Class 9c resident use area | N/A | 2.2 kW/m2 | 4.5 kW/m2 |
| Class 9c areas other than resident use areas | N/A | 1.2 kW/m2 | 4.5 kW/m2 |
Table for S7C3 Floor linings and floor coverings
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S7C3.