Victoria variation · NCC 2022 Volume One
VIC D2D5 Exit travel distances
Part D2 Provision for escape · varies D2D5 Exit travel distances
Delete subclause D2D5(4) and insert VIC D2D5(4) as follows:
(4) Class 9 buildings — in a patient care area in a Class 9a building and in a children’s service—
no point on the floor must be more than 12 m from a point from which travel in different directions to 2 of the required exits is available; and
the maximum distance to one of those exits must not be more than 30 m from the starting point.
Not in NCC 2025. No VIC D2D5 in NCC 2025 Volume One.