D2D5 Exit travel distances
Part D2 Provision for escape · NCC 2019: D1.4
(1) Class 2 and 3 buildings —
The entrance doorway of any sole-occupancy unit must be not more than—
6 m from an exit or from a point from which travel in different directions to 2 exits is available; or
20 m from a single exit serving the storey at the level of egress to a road or open space; and
no point on the floor of a room which is not in a sole-occupancy unit must be more than 20 m from an exit or from a point at which travel in different directions to 2 exits is available.
(2) Class 4 parts of a building — The entrance doorway to any Class 4 part of a building must be not more than 6 m from an exit or a point from which travel in different directions to 2 exits is available.
(3) Class 5, 6, 7, 8 or 9 buildings — Subject to (4), (5) and (6)—
no point on a floor must be more than 20 m from an exit, or a point from which travel in different directions to 2 exits is available, in which case the maximum distance to one of those exits must not exceed 40 m; and
in a Class 5 or 6 building, the distance to a single exit serving a storey at the level of access to a road or open space may be increased to 30 m.
(4) Class 9a buildings — In a patient care area in a Class 9a building—
no point on the floor must be more than 12 m from a point from which travel in different directions to 2 of the required exits is available; and
the maximum distance to one of those exits must not be more than 30 m from the starting point.
(5) Open spectator stands — The distance of travel to an exit in a Class 9b building used as an open spectator stand must be not more than 60 m.
(6) Assembly buildings — In a Class 9b building other than a school or early childhood centre, the distance to one of the exits may be 60 m if—
the path of travel from the room concerned to that exit is through another area which is a corridor, hallway, lobby, ramp or other circulation space; and
the room is smoke-separated from the circulation space by construction having an FRL of not less than 60/60/60 with every doorway in that construction protected by a tight fitting, self-closing, solid-core door not less than 35 mm thick; and
the maximum distance of travel does not exceed 40 m within the room and 20 m from the doorway to the room through the circulation space to the exit.