VIC F4D13 First aid rooms
Part F4 Sanitary and other facilities
Insert VIC clause F4D13 in clause F4D13 as follows:
(1) If an assembly building, place of public entertainment (as defined in the Building Act 1993) or an open spectator stand accommodates more than 5000 spectators at an arena, sportsground, showground, racecourse, cricket ground, football ground, coursing ground, motor racing arena, or the like, a suitable room or rooms must be provided in accordance with VIC Table F4D13 for use by para-medical attendants for first aid purposes.
(2) First aid rooms required by (1) must—
be distributed as uniformly as possible throughout the assembly building or open spectator stand; and
be convenient to a public road; and
be readily accessible from within and outside the arena or ground; and
have a floor area of not less than 24 m2; and
be provided with a suitable wash basin or sink.
Insert VIC table (F4D13) F4D13 as follows:
VIC Table F4D13: First aid rooms
Spectator capacity
Number of first aid rooms
5,001 to 10,000
1
10,001 to 15,000
2
15,001 to 30,000
3
Each extra 15,000 or part thereof
1