Victoria variation · NCC 2025 Volume One

VIC F4D13 First aid rooms

VIC Part F4 Sanitary and other facilities

Open on NCC Online ↗

Insert VIC clause F4D13 in clause F4D13 as follows:

(1) If an assembly building or an open spectator stand accommodates more than 5000 spectators at an arena, sportsground, showground, racecourse, cricket ground, football ground, coursing ground, motor racing arena, or the like, a suitable room or rooms must be provided in accordance with VIC Table F4D13 for use by para-medical attendants for first aid purposes.

(2) First aid rooms required by (1) must—

be distributed as uniformly as possible throughout the assembly building or open spectator stand; and

be convenient to a public road; and

be readily accessible from within and outside the arena or ground; and

have a floor area of not less than 24 m2; and

be provided with a suitable wash basin or sink.

Insert VIC table (F4D13) F4D13 as follows:

VIC Table F4D13: First aid rooms

Spectator capacity

Number of first aid rooms

5,001 to 10,000

1

10,001 to 15,000

2

15,001 to 30,000

3

Each extra 15,000 or part thereof

1

Changed since NCC 2022. See NCC 2022 Volume One VIC F4D13, or show what changed.