Victoria variation · NCC 2022 Volume One

VIC G5D2 Application of Part

Part G5 Construction in bushfire prone areas · varies G5D2 Application of Part

Open on NCC Online ↗

Delete clause G5D2 and insert VIC G5D2 as follows:

The Deemed-to-Satisfy Provisions of this Part apply in a designated bushfire prone area to—

a Class 2 or 3 building; or

a building located in an area subject to a Bushfire Attack Level (BAL) not exceeding BAL—12.5, determined in accordance with AS 3959 that is—

a Class 9a health-care building; or

a Class 9b—

an early childhood centre; or

a primary or secondary school; or

a Class 9c residential care building; or

a Class 10a building or deck immediately adjacent or connected to a—

Class 2 or 3 building; or

a building of a type listed in (b); or

a Class 4 part of a building associated with a building of a type listed in (b).

Notes

If a building of a type listed in (b), (c)(ii) or (d) is subject to a BAL exceeding BAL—12.5, the building would need to comply with Performance Requirement VIC G5P2 by means of a Performance Solution.

There are no Deemed-to-Satisfy Provisions for these buildings.

Not in NCC 2025. No VIC G5D2 in NCC 2025 Volume One.

The national clause