VIC I4D6 Electronic communication system
VIC Part I4 Class 3 and 9a residential aged care buildings and Class 9c buildings
A communication system must—
contain a back-up power supply; and
have a control that enables the call to be cancelled manually at the point of origin only; and
incorporate a device at the point of origin that indicates the system has operated; and
incorporate an indication panel in the manager’s office or staff area that clearly indicates the point of origin of a call; and
have an audible tone that has a continuous signal until deactivated at the point of origin; and
be operational at all times; and
have two call points in each ensuite or combined shower/water closet with one call point located in the shower recess and the other on the wall beside the closet pan ahead of the bowl rim; and
have call points (other than those mentioned in (g)) which are located—
within the reach of a resident whilst in bed; and
in all common habitable rooms; and
in all bathrooms, sanitary compartments and shower rooms where the call point must be of waterproof construction and within the reach of any fallen resident.