Western Australia variation · NCC 2022 Volume One

WA I4D6 Artificial lighting

WA Part I4 Public buildings

Open on NCC Online ↗

(1) Artificial lighting must be provided along the external path of travel (including steps, landings, ramps or paths) to a road or open space associated with each exit from a WA public building.

(2) The artificial lighting system required by (1) must—

provide a minimum illuminance of 1 lux at ground level; and

be connected to circuits separate from those supplying lighting for foyers, entry porches, emergency escape passages or areas provided entry or egress to the WA public building; and

be connected over two circuits where two or more lights are required; and

have switches that are not able to be operated by members of the public.

Changed in NCC 2025. See NCC 2025 Volume One WA I4D6, or show what changed.

Delete clause I4D6 and insert WA I4D6 as follows: (1) Artificial lighting must be provided along the external path … not able to be operated by members of the public.