Victoria variation · NCC 2022 Volume One

VIC S18C3 System requirements

Specification 18 Class 2 and 3 buildings not more than 25 m in effective height · varies S18C3 System requirements

Open on NCC Online ↗

Delete subclause S18C3(1) and insert VIC S18C3(1) as follows:

(1) A required automatic fire sprinkler system installed in a Class 2 or 3 building with an effective height of not more than 25 m and a rise in storeys of 4 or more must comply with—

AS 2118.1 except clause 5.9.10 of AS 2118.1 does not apply and is replaced with ‘Covered balconies shall be sprinkler protected’; or

AS 2118.4, as applicable; or

FPAA101D—

except for residential care building (Vic); and

except that clause 2.2.1 of FPAA101D applies as if the first paragraph is replaced with ‘Covered balconies shall be sprinkler protected’; or

FPAA101H—

except for residential care building (Vic); and

except that clause 3.5.2.8 of FPAA101H applies as if the first paragraph is replaced with ‘Covered balconies shall be sprinkler protected’; and

except that clause 3.5.3 of FPAA101H applies as if it is replaced with:

The location and spacing of sprinklers in Class 5, 6, 7, 8 and 9b parts of the building shall be in accordance with Section 5 of AS 2118.1:2017.

The location and spacing of sprinklers in Class 9a and 9c parts of the building shall be in accordance with Section 5 of AS 2118.1:2017 except that clause 5.9.10 of AS 2118.1 does not apply and is replaced with ‘Covered balconies shall be sprinkler protected’.

Not in NCC 2025. No VIC S18C3 in NCC 2025 Volume One.