S18C3 System requirements
Specification 18 Class 2 and 3 buildings not more than 25 m in effective height · NCC 2019: Spec E1.5a: 2
(1) A required automatic fire sprinkler system installed in a Class 2 or 3 building with an effective height of not more than 25 m and a rise in storeys of 4 or more must comply with—
AS 2118.1; or
AS 2118.4, as applicable; or
FPAA101D, except for residential care buildings; or
FPAA101H, except for residential care buildings.
(2) A Class 2 or 3 building not more than 25 m in effective height with a rise in storeys of 4 or more provided with an automatic fire sprinkler system under (1)(a) or (1)(b) may be constructed in accordance with S18C4(1), as applicable, provided—
the automatic fire sprinkler system is permanently connected to a fire alarm monitoring system connected to a fire station or fire station dispatch centre in accordance with Specification 23 if—
the system has more than 100 sprinkler heads; or
in the case of a residential care building, the building will accommodate more than 32 residents; and
the automatic fire sprinkler system is fitted with sprinklers complying with clauses 4.4, 4.5 and 5.5.2 of AS 2118.4 in bedrooms; and
an automatic smoke detection and alarm system is installed in accordance with Specification 20 except that it need not be connected to a fire alarm monitoring system connected to a fire station or fire station dispatch centre, and in the case of a residential care building it must be installed in accordance with—
S20C4; or
both—
S20C3, provided S20C3(1)(b) is applied as if the building was not protected with a sprinkler system; and
Specification 23; and
in a residential care building, the automatic smoke detection and alarm system and the automatic fire sprinkler system are connected to a local fire indicator panel provided in accordance with Specification 23; and
fire orders are provided in a Class 3 building in accordance with G4D8 as for a building in an alpine area.