Victoria variation · NCC 2022 Volume One

VIC S20C8 System monitoring

Specification 20 Smoke detection and alarm systems · varies S20C8 System monitoring

Open on NCC Online ↗

Delete clause S20C8 and insert VIC S20C8 as follows:

The following installations must be connected to a fire alarm monitoring system connected to a fire station or a fire station dispatch centre in accordance with AS 1670.3:

A smoke detection system in a Class 3 building provided in accordance with S20C2(b)(i) or (ii).

A smoke detection system in a Class 9a health-care building, if the building accommodates more than 20 patients, unless the building is sprinklered and the sprinkler system is permanently connected to a fire station, or other approved monitoring service with a direct data link to a fire station, in accordance with Building Practice Note FS-01.

Smoke detection in accordance with S20C6 provided to activate—

a smoke exhaust system in accordance with Specification 21; or

smoke-and-heat vents in accordance with Specification 22.

An automatic fire detection and alarm system required by E2D10 for large isolated buildings subject to C3D4.

Not in NCC 2025. No VIC S20C8 in NCC 2025 Volume One.