VIC S20C8 System monitoring
Specification 20 Smoke detection and alarm systems · varies S20C8 System monitoring
Delete clause S20C8 and insert VIC S20C8 as follows:
The following installations must be connected to a fire alarm monitoring system connected to a fire station or a fire station dispatch centre in accordance with AS 1670.3:
A smoke detection system in a Class 3 building provided in accordance with S20C2(b)(i) or (ii).
A smoke detection system in a Class 9a health-care building, if the building accommodates more than 20 patients, unless the building is sprinklered and the sprinkler system is permanently connected to a fire station, or other approved monitoring service with a direct data link to a fire station, in accordance with Building Practice Note FS-01.
Smoke detection in accordance with S20C6 provided to activate—
a smoke exhaust system in accordance with Specification 21; or
smoke-and-heat vents in accordance with Specification 22.
An automatic fire detection and alarm system required by E2D10 for large isolated buildings subject to C3D4.