Deemed-to-Satisfy Provision · NCC 2022 Volume Three

B1D2 Water efficiency

Part B1 Cold water services · NCC 2019: B1.2

Open B1D2 on NCC Online ↗
Varied in QLD. Check the variation for your state.

(1) A tap or outlet used for a shower, basin, kitchen sink or laundry trough must be a minimum of 3 Star WELS rated and discharge not more than 9 litres per minute.

(2) Cisterns or flushing devices for water closets must—

have a dual flushing mechanism; and

be a minimum 3 Star WELS rating discharging not more than 6 litres or 4.5 litres for a full flush.

(3) Cisterns or flushing devices for urinals must—

be a minimum 2 Star WELS rating discharging a volume of not more than 2.5 litres for each—

single urinal stall; or

600 mm length of continuous urinal wall; and

not be set-cycled or activated by any method other than manual or use activation.

Applications

B1D2(1) applies to outlets that provide cold water only. The Deemed-to-Satisfy Provision for outlets that deliver a combination of cold water and heated water is B2D4.

The flush volumes of B1D2(2) and B1D2(3) may be within a tolerance of—

±0.5 litres for the full flush of a 6/3 litre cistern; or

+0.5 litres for the reduced flush of a 6/3 litre cistern; or

±0.2 litres for a 4.5/3 litre cistern.

Exemptions

The requirements of B1D2(1) do not apply to a shower intended to provide rapid drenching of a person for emergency purposes, such as chemical removal.

The requirements of B1D2(2) and B1D2(3) do not apply to a vacuum drainage system.

The requirements of B1D2(3)(b) do not apply to a programmed solenoid operated flushing system if programmed to shut down during extended periods of non-occupancy of a building.

Same wording in NCC 2025 Volume Three. See NCC 2025 Volume Three B1D2.