NCC 2022 Volume Three
Part B1 Cold water services
16 clauses · Open on NCC Online ↗
- B1O1 ObjectiveThe Objective of this Part is to— safeguard people from illness, injury or loss (including loss of amenity) due to the failure of a cold water…
- B1F1 Cold water supplySanitary fixtures, sanitary appliances and supply outlets providing drinking water must have a safe and adequate piped cold water supply.
- B1F2 Cold water serviceThe cold water service must be conveyed through plumbing installations in a way that minimises any adverse impact on building occupants, the Network…
- B1F3 Fire sprinkler systemsResidential fire sprinkler equipment must be provided with adequate water supply and pressure for its intended purpose.
- B1P1 Cold water supplyA cold water service must be connected to a drinking water supply. Applications B1P1 applies to cold water supplied for human consumption, food…
- B1P2 VelocityCold water service pipework must ensure that the pipework water velocity does not exceed 3 metres per second for more than 1% of the time that water…
- B1P3 Access and isolationA cold water service must ensure access for maintenance of mechanical components and operational controls. (2) A cold water service must ensure the…
- B1P4 Water efficiencyA cold water service must ensure the efficient use of drinking water by— limiting water usage from— a tap or outlet for a shower, basin, kitchen…
- B1P5 Pressure TASThe points of discharge for a cold water service must— have— a working pressure of not less than 50 kPa; and a static pressure within the building…
- B1P6 Uncontrolled dischargeA cold water service must avoid failure or uncontrolled discharge.
- B1D1 Deemed-to-Satisfy ProvisionsPerformance RequirementB1P1 is satisfied if the cold water service is connected to— the Network Utility Operator’s drinking water supply; or an…
- B1D2 Water efficiency QLDA tap or outlet used for a shower, basin, kitchen sink or laundry trough must be a minimum of 3 Star WELS rated and discharge not more than 9 litres…
- B1D3 General requirements NSW TAS VICA cold water service must be in accordance with AS/NZS 3500.1.
- B1D4 Bushfire prone areasA cold water service in a designated bushfire prone area must be in accordance with AS 3959.
- B1D5 Cold water fire sprinkler systemsA cold water service used for fire-fighting must be in accordance with— the requirements of E1 of Volume One, where applicable; and FPAA 101D when…
- B1D6 Top-up linesA cold water service used to top up a rainwater tank must be in accordance with AS/NZS 3500.1.