Deemed-to-Satisfy Provision · NCC 2022 Volume Three

B1D5 Cold water fire sprinkler systems

Part B1 Cold water services · NCC 2019: B4.2

Open B1D5 on NCC Online ↗

A cold water service used for fire-fighting must be in accordance with—

the requirements of E1 of Volume One, where applicable; and

FPAA 101D when installed in a Class 2 or Class 3 building with an effective height of not more than 25 m and a rise in storeys of 4; and

AS/NZS 3500.1.

Exemptions

B1D5(b) does not apply to a residential care building.

Changed in NCC 2025 (minor wording). See NCC 2025 Volume Three B1D5, or show what changed.

A cold water service used for fire-fighting must be in … more than 25 m and a rise in storeys of 4; 4 or more; and AS/NZS 3500.1. Exemptions B1D5(b) does not apply to a residential care building.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Defined terms used