B2D2 Water heater in a heated water supply system
Part B2 Heated water services · NCC 2019: SA B2.2, TAS B2.2(1)(a) and (d), B2.2
(1) In a new Class 1 or Class 10 building, a water heater in a heated water supply system must be—
a solar water heater complying with (2); or
a heat pump water heater complying with (2); or
a gas water heater complying with (3); or
an electric resistance water heater only in the circumstances described in (4); or
a wood fired thermosiphon water heater or direct fired water heater each complying with AS/NZS 3500.4.
(2) In a new Class 1 or Class 10 building a solar water heater and a heat pump water heater must comply with either—
Table B2D2a, for the minimum Small-scale Technology Certificates for the installation zone; or
Table B2D2b, for the minimum energy savings calculated in accordance with AS/NZS 4234.
(3) In a new Class 1 or Class 10 building, a gas water heater must be rated not less than 5 Stars in accordance with AS 4552.
(4) In a new Class 1 or Class 10 building, an electric resistance water heater with no storage or a heated water delivery of not more than 50 litres in accordance with AS 1056.1 may be installed when—
the building has—
not more than 1 bedroom; and
not more than 1 electric resistance water heater installed; or
the building has—
a water heater that complies with (2) or (3); and
not more than 1 electric resistance water heater installed; or
the greenhouse gas emission intensity of the public electricity supply is low.
Table B2D2a Minimum Small Scale Technology Certificates
Number of bedrooms in the building
2022
2023
2024
2025
1 or 2
12
11
9
8
3 or 4
19
17
15
13
4 or more
25
22
19
16
Table B2D2b Minimum energy savings
Number of bedrooms
Minimum energy saving
1 or 2
40% for a ‘small load’ system
2 or 3
60% for a ‘medium load’ system
4 or more
60% for a ‘large load’ system
Tables
Changed in NCC 2025. See NCC 2025 Volume Three B2D2, or show what changed.
(1) In a new Class 1 or Class 10 building, … Small Scale Technology Certificates Number of bedrooms in the building 2022 2023 2024 2025 2026 2027 2028 1 or 2 12 11 9 8 7 5 4 3 or 4 19 17 15 13 11 8 6 4 or more 25 22 19 16 14 11 8 Table B2D2b Minimum energy savings Number of bedrooms Minimum energy … system 4 or more 60% for a ‘large load’ system Limitations B2D2 does not apply where compliance with H6P2 of Volume Two is achieved by complying with S42C3 using house energy rating software and S42C4(2).
Removed words are struck through; added words are highlighted. Comparison of the text only.
State and territory variations all clauses side by side →
- NSW Varied This clause been deliberately left blank Compliance is not required with the national provisions of B2D2 as the sources of…
- QLD Varied This clause been deliberately left blank
- SA Replaced Delete clause B2D2 and insert SA B2D2 as follows: (1) In an established Class 1 building connected to a reticulated gas supply…
- TAS Replaced Delete clause B2D2 and insert TAS B2D2 as follows: In a new Class 1 or Class 10 building— a water heater in a heated water…
- VIC Added Insert VIC subclause B2D2(5) in clause B2D2 as follows: (5) A solar water heater system installed in a new Class 1 building to…