Performance Requirement · NCC 2022 Volume Three

B2P3 Velocity

Part B2 Heated water services · NCC 2019: BP2.3

Open B2P3 on NCC Online ↗
Varied in VIC. Check the variation for your state.

The water velocity in heated water service pipework up to 65 °C must not exceed—

3.0 m/s for more than 1% of the time that water is required during the peak hour in reticulated heated water systems; and

1.2 m/s for the flow and 1.0 m/s for the return of a copper circulatory heated water service for more than 1% of the time that water is required during the peak hour; and

1.0 m/s for the flow and return of a circulatory heated water service using other materials for more than 1% of the time that the water is required during the peak hour.

Changed in NCC 2025. See NCC 2025 Volume Three B2P3, or show what changed.

The water velocity in heated water service pipework up to 65 °C must not exceed — 3.0 m/s for more no less than 1% 99% of the time that water is required during the peak hour in reticulated non-circulatory heated water systems; and 1.2 m/s for the flow and 1.0 m/s for the return of a copper circulatory heated water service for more no less than 1% 99% of the time that water is required during the peak hour; and 1.0 2.0 m/s for the flow and 1.0m/s for the return of a circulatory heated water service using other materials for more no less than 1% 99% of the time that the water is required during the peak hour.

Removed words are struck through; added words are highlighted. Comparison of the text only.

State and territory variations all clauses side by side →