B2P3 Velocity
Part B2 Heated water services · NCC 2019: BP2.3
The water velocity in heated water service pipework up to 65 °C must not exceed—
3.0 m/s for no less than 99% of the time that water is required during the peak hour in non-circulatory heated water systems; and
1.2 m/s for the flow and 1.0 m/s for the return of a copper circulatory heated water service for no less than 99% of the time that water is required during the peak hour; and
2.0 m/s for the flow and 1.0m/s for the return of a circulatory heated water service using other materials for no less than 99% of the time that the water is required during the peak hour.
Changed since NCC 2022. See NCC 2022 Volume Three B2P3, or show what changed.
The water velocity in heated water service pipework up to 65 °C must not exceed — 3.0 m/s for more no less than 1% 99% of the time that water is required during the peak hour in reticulated non-circulatory heated water systems; and 1.2 m/s for the flow and 1.0 m/s for the return of a copper circulatory heated water service for more no less than 1% 99% of the time that water is required during the peak hour; and 1.0 2.0 m/s for the flow and 1.0m/s for the return of a circulatory heated water service using other materials for more no less than 1% 99% of the time that the water is required during the peak hour.