Victoria variation · NCC 2022 Volume Three

VIC B2P3 Velocity

Part B2 Heated water services · varies B2P3 Velocity

Open on NCC Online ↗

Delete subclause B2P3(1) and insert VIC B2P3(1) as follows:

The water velocity in heated water service pipework up to 65 °C must not exceed—

3 m/s for more than 1% of the time that water is required during the peak hour in non-circulatory heated water systems; and

1.2 m/s for the flow and 1.0 m/s for the return of a copper circulatory heated water service for more than 1% of the time that water is required during the peak hour; and

1.0 m/s for the flow and return of a circulatory heated water service using other materials for more than 1% of the time that the water is required during the peak hour.

Not in NCC 2025. No VIC B2P3 in NCC 2025 Volume Three.